The document describes an extended-phase-shift (EPS) control method for isolated bidirectional DC-DC converters used in power distribution for microgrids. EPS control adds an inner phase-shift ratio between switch driving signals in addition to the outer phase-shift ratio of traditional phase-shift control. This decreases the backflow power effect seen in traditional control, expanding the power regulating range and reducing current stress compared to traditional control. The document analyzes the operation principle and eight modes of the converter under EPS control through circuit diagrams and mathematical equations.
2. 4668 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 1. Typical application of BDC for power distribution in microgrid [11].
Fig. 2. Typical configuration of IBDC.
In TPS control [14]–[16], [20], the cross-connected switch
pairs in both H-bridges (H1 and H2 ) are switched in turn to gen-erate
phase-shifted transition square waves to the transformer’s
primary and secondary sides. And the corresponding phase shift
changes the voltage across the transformer’s leakage inductor to
manipulate the power flowdirection and magnitude. This control
method is attracting more and more attention due to its advan-tages
such as small inertia, high dynamic performance, easy to
realize soft-switching control, and so on. But in this method, the
control of the power flow is dependent on transformer’s leak-age
inductor that result in great circulating power and current
stress when the value of V1 /nV2 deviate far from 1, where n is
turns’ ratio of the transformer. And then, the loss in power de-vices
and magnetic components is increased and the efficiency
of converter is reduced. In order to improve the performance of
the IBDC, various control methods were explored [21]–[25]. In
some of these studies [21], [22], the duty ratio of the driving
signals of each semiconductor device is variable, and should be
calculated online, that increases the complexity of the control.
Some studies are focused on how to extend the soft-switching
range [23] or eliminate reactive power [24], the detailed anal-ysis
of steady characteristics is not conducted. In [25], a novel
phase-shift dual-half-bridge converter with an adaptive inductor
was proposed. It utilizes an adaptive inductor as the commuta-tion
inductor to adapt to the change of the output power, which
results in strict requirements of the coiling method of inductor
and the complexity of the control. And it is mainly improve-ment
of hardware design; the control method of the proposed
converter is still TPS control.
In view of the study situation mentioned above, this paper
points out a phenomenon of power backflowin traditional phase-shift
control, and analyzes the effects which backflow power act
Fig. 3. Equivalent circuit of phase-shift control.
on power circulating flow and current stress. On this basis, the
paper presents a novel extended-phase-shift control of IBDC
for power distribution in microgrid. Different from the control
methods mentioned above, this method adds another degree of
freedom to the converter by adjusting the time sequence between
the driving signals of diagonal semiconductor switches, e.g.,
(S1, S4 ) in Fig. 2. It not only has smaller power circulating
flow and current stress, but also expands regulating range of
transmission power and enhances regulating flexibility.
II. PHENOMENON OF POWER BACKFLOW IN TRADITIONAL
PHASE-SHIFT CONTROL
In Fig. 2, we replace the transformer with T-type equivalent
circuit, and considering that the magnetizing inductance of the
transformer is much greater than its leakage inductance, the
magnetizing inductance can be considered as an open circuit.
Therefore, the converter in phase-shift control can be repre-sented
by a simplified scheme comprised of two square waves
voltage sources linked by an inductance L, as shown in Fig. 3.
In Fig. 3, L is the sum of the transformer leakage inductance
and that of the auxiliary inductor L1 , vh1 and vh2 are the equiv-alent
AC output voltages of H1 and H2 in V1 side, respectively,
vL and iL are the voltage and current of inductor L, respectively.
The power-flow direction and magnitude can simply be con-trolled
by adjusting the phase shift between vh1 and vh2. Here
we take the forward power flow (from V1 to V2 ) as an example
to analyze the main operation principle of TPS control.
The main waveforms of IBDC in TPS control are shown
in Fig. 4, where pin is the transient waveform of transmission
power, Ths is a half switching period, and D is the phase-shift
ratio between the primary and secondary voltages of the isola-tion
transformer, where 0 ≤ D ≤ 1.Andwe assume V1 ≥ nV2 in
Fig. 4, the other condition V1 < nV2 can be analyzed similarly.
Because vh1 and vh2 are both square wave AC voltages and their
3. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4669
Fig. 4. Waveforms of IBDC in TPS control.
interaction is through the inductor L, so the phase of the primary
current is not always the same as the primary voltage. As can
be seen from Fig. 4, iL is of the opposite phase from vh1 for an
interval of t = t0 ∼ t
0 and t = t2 ∼ t
2 , that is a portion of the
power delivered to the V2 side in one switching period, while
the other portion is sent back to the primary voltage source V1 .
We defined it as backflow power, which is the dark-shaded area
in Fig. 4. For a given transmission power, with the increase of
the backflow power, the forward power also increases to com-pensate
the loss caused by backflow power. Then the circulating
power and current stress are increased, which result in great loss
in power devices and magnetic components and low efficiency
of converter [16], [19]–[23]. In Section IV, we will establish a
mathematical model to analyze it.
III. OPERATION PRINCIPLE OF EXTENDED-PHASE-SHIFT
CONTROL
A. Extended-Phase-Shift Control
In order to significantly decrease the backflow power of the
converter, vh1 should not be confined to square waveforms with
Fig. 5. Waveforms of IBDC in EPS control.
50% duty ratio. For example, if S1 and S4 do not have the same
driving signal but have a phase-shift ratio of D1, as shown in
Fig. 5, the transformer primary voltage will emerge as a three-level
instead of the traditional two-level. Then the behaviors
of iL will also be changed: the backflow-appearance time (t =
t0 ∼ t
0 and t = t2 ∼ t
2 ) in Fig. 4 are divided into two intervals
(t = t0∼t1 , t = t1 ∼ t
1 and t = t3∼t4 , t = t4 ∼ t
4) in Fig. 5,
respectively. And the transformer primary voltage vh1 = 0, i.e.,
backflow power is 0, when t = t0∼t1 and t = t3∼t4. So the
backflow power is decreased for a given transmission power. In
the reverse power flow, we just need to exchange the operating
states of the H-bridges H1 and H2 .
In Fig. 5, D1 is the phase-shift ratio between the driving sig-nals
of S1 and S4 or S 2 and S3 in H-bridge H1 , we defined its
inner phase-shift ratio, where 0 ≤ D1 ≤ 1. D2 is the phase-shift
4. 4670 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 6. Operation modes of IBDC in EPS control. (a) Mode 1. (b) Mode 2. (c) Mode 3. (d) Mode 4. (e) Mode 5. (f) Mode 6. (g) Mode 7. (h) Mode 8.
ratio between the primary and secondary voltages of the isola-tion
transformer, we defined its outer phase-shift ratio, where
0 ≤ D2 ≤ 1 and 0 ≤ D1+D2 ≤ 1. In fact, compared to the
TPS control, there is not only the outer phase-shift ratio but also
the inner phase-shift ratio in the proposed EPS control, which
will decrease the current stress, expands regulating range of
transmission power and enhances regulating flexibility.
B. Operation Modes of IBDC in Extended-Phase-Shift Control
To simplify the process of the analysis, we assume that the
converter has reached steady operation states. From Fig. 5, the
switching cycle can be divided into eight operation modes which
are explained as follows:
1) Mode 1 (t0–t1 ): Fig. 6(a) shows the equivalent circuit for the
mode 1. Just before t0, S2 and S3 are conducting. The current iL
is in negative direction. At t0, S3 is turned OFF and S4 is turned
ON at zero current, and D4 starts to conduct. On the secondary
side, the current is carried from L to V2 by M2 and M3. The
voltage across L is clamped at nV2 , and the current iL decreases
linearly. This mode ends up when S2 is turned OFF. During this
mode, the current of L is
iL (t) = iL (t0) + nV2
L
(t − t0 ). (1)
2) Mode 2 (t1–t
1 ): Fig. 6(b) shows the equivalent circuit for
mode 2. If current iL is still in negative direction at t1 then at
t1, S2 is turned OFF and S1 is turned ON at zero current, iL
is carried from L to V1 by D1 and D4 . On the secondary side,
the current is carried from L to V2 by M2 and M3 . The voltage
across L is clamped at V1+nV2 , and iL still decreases linearly.
This mode ends up with iL decreasing to zero. During this mode,
iL is
iL (t) = iL (t1) + V1 + nV2
L
(t − t1 ). (2)
5. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4671
3) Mode 3 (t
1–t2 ): Fig. 6(c) shows the equivalent circuit for
the mode 3. At t
1 , the polarity of iL changes from negative to
positive. And because the driving signals of S1, S4, Q2 , and
Q3 are already on, so S1, S4, Q2 , and Q3 start to conduct.
The voltage across L is clamped at V1 + nV2 , and iL increases
linearly. This mode ends up when Q2 and Q3 are turned OFF.
During this mode, iL is the same with (2).
4) Mode 4 (t2 – t3 ): Fig. 6(d) shows the equivalent circuit for
the mode 4. At t2, Q2 and Q3 are turned off and Q1 and Q4
are turned on at zero current. M1 and M4 start to conduct. The
voltage across L is clamped at V1–nV2 , and iL still increases
linearly due to V1 ≥ nV2 . This mode ends up when S4 is turned
OFF. During this mode, iL is
iL (t) = iL (t2) + V1 − nV2
L
(t − t2 ). (3)
5) Mode 5 (t3 – t4 ): Fig. 6(e) shows the equivalent circuit for
mode 5. At t3, S4 is turned OFF and S3 is turned ON at zero
current, D3 starts to conduct. On the secondary side, the current
is carried from L to V2 by M1 and M4 . The voltage across L
is clamped at –nV2 , and the current iL decreases linearly. This
mode ends up when S1 is turned OFF. During this mode, the
current of L is
iL (t) = iL (t3) +
−nV2
L
(t − t3 ). (4)
6) Mode 6 (t4 – t
4 ): Fig. 6(f) shows the equivalent circuit for
mode 6. If current iL is still in positive direction at t4 , then at
t4, S2 is turned OFF and S1 is turned ON at zero current, iL
is carried from L to V1 by D2 and D3 . On the secondary side,
the current is carried from L to V2 by M1 and M4 . The voltage
across L is clamped at –V1–nV2 , and iL still decreases linearly.
This mode ends up with iL decreasing to zero. During this mode,
iL is
iL (t) = iL (t4) +
−V1 − nV2
L
(t − t4 ). (5)
7) Mode 7 (t
4–t5 ): Fig. 6(g) shows the equivalent circuit for
the mode 7. At t
4 , the polarity of iL changes from positive to
negative. And, because the driving signals of S2, S3, Q1 , and
Q4 are already ON, so S2, S3, Q1 , and Q4 start to conduct.
The voltage across L is clamped at –V1–nV2 , and iL increases
linearly. This mode ends up when Q1 and Q4 are turned OFF.
During this mode, iL is the same with (5).
8) Mode 8 (t5 – t6 ): Fig. 6(h) shows the equivalent circuit for
the mode 8. At t5, Q1 and Q4 are turned OFF and Q2 and Q3
are turned ON at zero current. M2 and M3 start to conduct. The
voltage across L is clamped at –V1+nV2 , and iL still increases
linearly due to V1 ≥ nV2 . This mode ends up when S3 is turned
OFF. During this mode, iL is
iL (t) = iL (t5) +
−V1 + nV2
L
(t − t5 ). (6)
According to the above analysis, the transformer primary
voltage vh1 = 0, and there is no backflow power in modes 1
and 5. So the whole backflow power is decreased for a given
transmission power. In fact, if iL has dropped to zero before t1
or t4 , then the backflow power will be eliminated, as shown in
Fig. 7(a). In this case, modes 2 and 6 in Fig. 6 will be replaced
by mode 2 and 6 in Fig. 7(b) and (c), respectively.
9) Mode 2 (t
1–t1 ): Fig. 7(b) shows the equivalent circuit
for mode 2. At t
1 , the polarity of iL changes from negative
to positive. And because the driving signals of S2, S4, Q2 , and
Q3 are already ON, so D2, S4, Q2 , and Q3 start to conduct.
The voltage across L is clamped at nV2 , and iL still increases
linearly. This mode ends up when S2 is turned OFF. During this
mode, iL is the same with (1).
10) Mode 6 (t
4–t4 ): Fig. 7(c) shows the equivalent circuit
for mode 6. At t
4 , the polarity of iL changes from positive to
negative. And because the driving signals of S1, S3, Q1 , and
Q4 are already ON, so D1, S3, Q1 , and Q4 start to conduct.
The voltage across L is clamped at –nV2 , and iL still increases
linearly. This mode ends up when S1 is turned OFF. During this
mode, iL is the same with (4).
IV. ANALYSIS AND COMPARISONS OF TPS AND EPS CONTROL
A. Low-Frequency Average Model
According to the above analysis, assuming t0 = 0, then we
have t1 = D1Ths, t2 = D2Ths, t3 = Ths, t4 = Ths+D1Ths, t5 =
Ths+D2Ths, and t6 = 2Ths. The average current of the inductors
over one switching period (2Ths) should be zero in steady state;
thus from (1) to (6), we can derive
iL (t0) = − nV2
4fsL
[k(1 − D1) + (2D1 + 2D2 − 1)] (7)
iL (t1) = − nV2
4fsL
[k(1 − D1) + (2D2 − 1)] (8)
iL (t2) = nV2
4fsL
[k(2D2 + D1 − 1) + 1] (9)
where fs = 1/(2Ths) is switching frequency, k = V1/nV2 is the
voltage conversion ratio, and we assume k ≥ 1 in the paper,
the other condition k 1 can be analyzed similarity. When the
power flows from V1 to V2 , the current stress of converter under
EPS control is
max = |iL (t0 )| = nV2
i
4fsL
[k(1 − D1) + (2D1 + 2D2 − 1)].
(10)
The transmission power is
P
=
1
Ths
Th s
0
vh1iL (t)dt
= nV1V2
2fsL
D2(1 − D2) +
. (11)
1
2D1(1 − D1 − 2D2 )
6. 4672 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 7. (a) Waveforms of IBDC in EPS control when the backflow power is zero. (b) Mode 2 of IBDC in EPS control when the backflow power is zero. (c)
Mode 6 of IBDC in EPS control when the backflow power is zero.
The backflow power is
P
bf =
1
Ths
t
1
t1
vh1 |iL (t)|dt
= nV1V2 [k(1 − D1) + (2D2 − 1)]2
16fsL(k + 1)
(12)
where iL (t1 ) 0, from (8), we have
k
1 − 2D2
1 − D1
. (13)
When k ≤ (1–2D2 )/(1–D1 ), the backflow power is zero. In (7)–
(13), the constraints are k ≥ 1, 0 ≤ D1 ≤ 1, 0 ≤ D2 ≤1, and
0 ≤ D1+D2 ≤ 1. Similarly, from Fig. 4, the current stress of
converter under TPS control is
imax = nV2
4fsL
(2D − 1 + k). (14)
The transmission power is
P = nV1V2
2fsL
D(1 − D). (15)
The backflow power is
Pbf = nV1V2 [k + (2D − 1)]2
16fsL(k + 1) . (16)
In (14)–(16), the constraints are k ≥ 1 and 0 ≤ D ≤ 1.
Theoretically, when the load is set as resistance R, from (11),
we can derive
V2 = nV1R
2fsL
D2(1 − D2) +
1
2D1(1 − D1 − 2D2 )
. (17)
With the variation of D1 and D2, we have
0 ≤ V2 ≤ nV1R
8fsL
. (18)
Similarly, from (15), the output voltage range in the TPS control
can be achieved. In fact, the output voltage range in the EPS
control is the same as that in the TPS control. And its main
benefit lies in that the power circulating flow and current stress
are both reduced for a given output power; therefore, it leads
to the improvement of the converter’s overall efficiency. Theory
and experiment analysis of the paper are centering on these
special characteristics of EPS control as well.
B. Comparative Analysis of Transmission Power
For the convenience of analysis, the unified transmission
power p and p are defined as
⎧⎪⎪⎨
⎪⎪⎩
p = P
PN
= 4D2(1 − D2) + 2D1(1 − D1 − 2D2 )
p = P
PN
= 4D(1 − D)
(19)
7. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4673
Fig. 8. Relation curves of the unified transmission power p with D1 and D2 . (a) 3-D curves. (b) 2-D curves.
where
PN = nV1V2
8fsL
. (20)
When taking that the outer phase-shift ratio (D2) in EPS
control is equal to the phase-shift ratio (D) in TPS control, the
3-D curves of the unified transmission power p and p varied with
D1 andD2 shown in Fig. 8(a). As can be seen from Fig. 8(a), with
different D1 , p will be different with p. And the EPS control
can achieve larger transmission power than the TPS does when
0 ≤ D2 0.5. In fact, from (19), we can derive
p
max = 1− (1 − 2D2 )2
2
(21)
where 0 ≤ D2 0.5 and D1 = (1-2D2 )/2.
p
max = 4D2(1 − D2 ) (22)
where 0.5 ≤ D2 1 and D1 = 0.
p
min = 2D2(1 − D2 ) (23)
where D1 = 1-D2 .
From (21) to (23), Fig. 8(a) can be converted to a 2-D picture,
as shown in Fig. 8(b). The dashed line is the regulating curve
of transmission power in TPS control, and the dark-shaded area
is the regulating area of transmission power in EPS control.
From Fig. 8(b), due to the addition of D1 , the regulating range
of transmission power is changed from the single curve to the
2-D area. With the same outer phase-shift ratio (D2 = D), the
EPS control offers wider power transmission range than the TPS
control does, and the maximum value is determined by (21) and
(22) while the minimum value is determined by (23). Due to the
addition of D1 , the regulating flexibility of transmission power
is also enhanced.
Considering that the basic prerequisite for comparative analy-sis
of backflow power and current stress is that the transmission
power of TPS and EPS control are the same. In the follow-ing
analysis, we take operating points A/A4 , B/B3 , and C/C2 as
characteristic points of TPS control in different operating ar-eas,
where A(D = 1/8), A4 (D = 7/8), B(D = (2 − 21/2)/4),
B3 (D = (2+21/2)/4), C(D = 1/4), and C2 (D = 3/4), then the
characteristic points of EPS control are A1 /A2 /A3 , B1 /B2 , and
C1 .
C. Comparative Analysis of Backflow Power
Considering the relationship between the backflow power
and the transmission power, the unified backflow power Mbf
and M
bf are defined as
M
bf =
P
bf
PN
=
[k(1 − D1) + (2D2 − 1)]2
2(k + 1)
(24)
Mbf = Pbf
PN
=
[k + (2D − 1)]2
2(k + 1) . (25)
The basic prerequisite for comparative analysis of backflow
power is that the transmission power of TPS and EPS control
are the same. From (11) and (15), we have
4D(1 − D) = 4D2(1 − D2) + 2D1(1 − D1 − 2D2 ). (26)
With the specified value of D1 and D2 in EPS control, the
phase-shift ratio D in TPS control can be obtained
D=
⎧⎪⎪⎨
⎪⎪⎩
D =
1 −
1 − 4D2(1 − D2 ) − 2D1(1 − D1 − 2D2 )
2
D =
1 +
1 − 4D2(1 − D2 ) − 2D1(1 − D1 − 2D2 )
2
.
(27)
Using (24), (25), and (27), and assuming k = 5, the 3-D curve of
the unified backflow power varied with D1 and D2 can be shown
in Fig. 9. As can be seen from Fig. 9, the backflow power in
TPS and EPS control are the same when D1 = 0. And due to the
addition of D1 , with the same transmission power, the backflow
power in TPS control is larger than that in EPS control, and the
condition of D = D generates larger backflow power than the
condition of D = D does.
The contour lines in Fig. 8(b) show that there are infinite
combinations of (D1 , D2 ) in EPS control for the same transmis-sion
power in TPS control. Considering the different qualities
of EPS control in different operating points, we will analyze the
8. 4674 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 9. 3-D curves of the unified backflow power M
bf varied with D1 and
D2 .
optimal operating point of backflow power. From (26), we have
D1 =
⎧⎪⎪⎨
⎪⎪⎩
D1
=
1 − 2D2 −
2(1 − 2D)2 − (1 − 2D2 )2
2
D
1 =
1 − 2D2 +
2(1 − 2D)2 − (1 − 2D2 )2
2
.
(28)
For D
1 ≥ D1
, from (24), we have
M
bf (D
1
) ≥ M
bf (D
1 ). (29)
Substituting D1 = D
1 into (24), the function of M
bf and D2
can be obtained
M
bf min(D2 )
=
[k(1−
2(1 − 2D)2−(1 − 2D2 )2)+ 2(k + 2)D2 − 2]2
8(k + 1)
(30)
where |1–2D2| ≤ 21/2 |1–2D| and 0 ≤ D2 ≤ 1. Solving (30)
with constrained optimization methods, we can derive
1) when 0 ≤ D (2–21/2)/4
M
bf min(D2)=M
bf min(0) =
[k − 2 − k
2(1 − 2D)2 − 1]2
8(k + 1)
(31)
where
⎧⎨
⎩
D1 =
1 +
2(1 − 2D)2 − 1
2
D2 = 0
(32)
2) when (2–21/2)/4 ≤ D 1/2
M
bf min(D2) = M
bf min
1 −
√
2(1 − 2D)
2
=
√
2 − 1)k − 2 + 2(k + 2)D]2
[(
4(k + 1)
(33)
where
⎧⎪⎪⎨
⎪⎪⎩
D1 =
√
2(1 − 2D)
2
D2 =
1 −
√
2(1 − 2D)
2 .
(34)
In Fig. 8(b), we take operating points A, B, C, A1 /A2 /A3 , B1 /B2 ,
and C1 as characteristic points of TPS and EPS control in differ-ent
operating areas, from (19) to (21), and (26), we have: A1 (D2
= 0, D1 = (4+21/2)/8), A1
(D2 = 0, D1 = (4–21/2)/8), A2 (D2
= (4–21/2)/8, D1 = (4+21/2)/8), A3 (D2 = (4+21/2)/8, D1 =
(4–21/2)/8), B1 (D2 =0,D1 =1/2), B2 (D2 =1/2,D1 =1/2), and
C1 (D2 = (2–21/2)/4, D1 = 21/2/4). Fig. 10 shows the curves of
the unified backflow power varied with voltage conversion ratio
k in TPS and EPS control for the same transmission power.
D. Comparative Analysis of Current Stress
For the convenience of analysis, the unified current stress G
and G are defined as
G
= i
max
IN
= 2[k(1 − D1) + (2D1 + 2D2 − 1)] (35)
G = imax
IN
= 2(2D − 1 + k) (36)
where
IN = PN
V1
= nV2
8fsL
. (37)
Using (27), (35), and (36), and assuming k = 5, the 3-D curve
of the unified current stress varied with D1 and D2 as shown in
Fig. 11. As can be seen from Fig. 11, the current stress in TPS
and EPS control are the same when D1 = 0. And due to the
addition of D1 with the same transmission power, the current
stress in TPS control is larger than that in EPS control, and the
condition of D = D generates larger current stress than the
condition of D = D does.
Likewise, the optimal operating point of current stress can be
analyzed. For D
1 ≥ D1
, from (35), we have
9. G(D1
) ≤ G(D
1 ) k 2
G(D
1 ) ≤ G(D1
) k ≥ 2.
(38)
That is,
min(D2) =
G
⎧⎪⎪⎨
⎪⎪⎩
2(1 − 2D)2 − (1 − 2D2 )2
(k − 2)
+2kD2 +k k2
2(1 − 2D)2 − (1 − 2D2 )2
(2 − k)
+2kD2 +k k≥ 2
(39)
where |1–2D2| ≤ 21/2 |1–2D| and 0 ≤ D2 ≤ 1. Solving (39)
with constrained optimization methods, we can derive
1) when 0 ≤ D (2–21/2)/4
min(D2) =
G
2(1 − 2D)2 − 1 +k k2
(k − 2)
2(1 − 2D)2 − 1 +k k≥ 2
(2 − k)
(40)
10. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4675
Fig. 10. Curves of the unified backflow power M
bf varied with voltage conversion ratio k. (a) A and A4 in TPS control and A1 , A
1 , A2, and A3 in EPS control.
(b) B and B3 in TPS control and B1 and B2 in EPS control. (c) C and C2 in TPS control and C1 in EPS control.
Fig. 11. 3-D curves of the unified current stress G varied with D1 and D2 .
where
⎧⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎩
D1 =
⎧⎪⎪⎨
⎪⎪⎩
1 −
2(1 − 2D)2 − 1
2 k 2
1 +
2(1 − 2D)2 − 1
2 k ≥ 2
D2 = 0.
(41)
According to (32) and (41), when k≥2, the optimal operating
points of backflow power and current stress are the same. From
(36) and (40), we can derive
11. G ≤ G
min k k0
G
min
≤G k≥ k0
(42)
k0 = 2− 1 +
2(1 − 2D)2 − 1
2(1 − D)
(43)
2) when (2–21/2)/4 ≤ D 1/2
min(D2) = k(2
G
√
2D + 2 −
√
2) (44)
where
⎧⎪⎪⎨
⎪⎪⎩
D1 =
√
2(1 − 2D)
2
D2 =
1 −
√
2(1 − 2D)
2 .
(45)
From (36) and (44), we can derive
12. G ≤ G
min k k0
G
min
≤G k≥ k0
(46)
where
k0 =
√
2. (47)
According to the above analysis, when k ≥ k0 , the current stress
in EPS control is less than that in TPS control. Likewise, we take
operating points A, B, C, A1 /A2 /A3 , B1 /B2 , and C1 as character-istic
points of TPS and EPS control in different operating areas.
Then the curves of the unified current stress varied with voltage
conversion ratio k for the same transmission power shown in
Fig. 12.
As can be seen from Fig. 12, in all operating areas, the current
stress increases with the increase of voltage conversion ratio k.
The EPS control can take different operating points to ensure
that the current stress is less than the TPS control when k ≥ k0 ,
and the minimum value is obtained at A1 , B1 , and C1 , which
agrees well with the aforementioned theoretical analysis.
V. EXPERIMENTAL RESULTS
In order to verify the aforementioned analysis, a laboratory
prototype is constructed based on TMS320F2812 DSP. And the
main parameters of converter are shown in Table I.
In order to verify the power regulating capacity of EPS con-trol,
the input voltage and the output load are specified as 220V
and 6 Ω, respectively. Fig. 13 shows the curves of the transmis-sion
power varied with D1 and D2 . As can be seen from Fig. 13,
in EPS control, the transmission power can be regulated both by
D1 and D2 , and due to the addition of D1 , the regulating range
13. 4676 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 12. Curves of the unified current stress G varied with voltage conversion ratio k. (a) A and A4 in TPS control and A1 , A1
, A2 , and A3 in EPS control. (b) B
and B3 in TPS control and B1 and B2 in EPS control. (c) C and C2 in TPS control and C1 in EPS control.
Fig. 13. Curves of the transmission power varied with D1 and D2 . (a) Curves of the transmission power varied with D1 when D2 is specified. (b) Curves of the
transmission power varied with D2 when D1 is specified.
TABLE I
MAIN PARAMETERS OF PROTOTYPE
of transmission power is changed from the single curve to the
2-D area.With the same outer phase-shift ratio (D2 = D 0.5),
the EPS control (D1= 0) can offer wider power transmission
range than the TPS control (D1 = 0) does, that will enhance
regulating flexibility. In addition, Fig. 13 shows that there are
many different combinations of (D1 , D2 ) in EPS control for the
same transmission power in TPS control. And the maximum
and minimum values of transmission power are obtained about
at D1+D2 = 0.5 and D1+D2 = 1, respectively, which agrees
well with the aforementioned theoretical analysis.
In order to verify the backflow power characterization of EPS
control, the transmission power and output voltage are both
in closed-loop control for 380W and 48V, respectively, the
transient waveforms of transmission power with input voltage
V1 = 220V is shown in Fig. 14(a), and the curves of backflow
power varied with input voltage V1 and inner phase-shift ratioD1
is shown in Fig. 14(b). It can be seen from Fig. 14, the backflow
power is bound up with input voltage V1 and inner phase-shift
ratio D1 , and it decreases with the increase of D1 and increases
with the increase of voltage conversion ratio k = V1 /(nV2 ).
Under different experimental conditions, the EPS control always
can generate less backflow power than the TPS control does, and
the minimum point of current stress is the minimum point of
14. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4677
Fig. 14. (a) Transient waveforms of the transmission power when D1 is specified. (b) Curves of the backflow power varied with V1 when D1 is specified.
Fig. 15. Waveforms of vh1 , vh 2 , and iL in TPS and EPS control for the same transmission. (a) TPS control with V1 = 220V, V2 = 48V, and P = 380W. (b)
EPS control with V1 = 220V, V2 = 48V, P = 380W, and D1 = 0.2. (c) EPS control with V1 = 220V, V2 = 48V, P = 380W, and D1 = 0.4.
backflow power when V1 200 (i.e., k200/(2∗48)≈2), which
agrees well with the aforementioned theoretical analysis.
Fig. 15 shows the experimental waveforms of vh1, vh2 , and
iL in TPS and EPS control for the same transmission power, and
Fig. 16 shows the curves of current stress varied with V1 and
D1 . It can be seen that current stress is also bound up with input
voltage V1 and inner phase-shift ratio D1 , and it decreases with
the increase of D1 and increases with the increase of voltage
conversion ratio k = V1 /(nV2 ). Under different experimental
conditions, the EPS control always can generate less current
stress than the TPS control does.When the converter is operating
in the optimal point, the stress current achieves the minimum
value, which is consistent with the aforementioned theoretical
analysis.
Under the same experimental conditions with Figs. 14(b) and
16, Fig. 17 shows the efficiency curves of the converter in both
control methods. It can be easily found that the EPS control
can achieve higher efficiency than the TPS control, especially in
large voltage conversion ratio condition. And when the converter
Fig. 16. Curves of the current stress varied with V1 when D1 is specified.
15. 4678 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
Fig. 17. Curves of the efficiency curves varied with V1 when D1 is specified.
Fig. 18. Waveforms of IBDC in EPS control when k 1.
is operating in the optimal point, the efficiency achieves the
maximum value.
VI. DISCUSSION
All of the above analysis is based on the qualification that k ≥
1. In fact, when k 1 (nV2 V1 ), we just need to exchange the
operating modes of the left and the right H-bridges, as shown in
Fig. 18.
Similar to the analysis in Sections I and IV, we can derive that
the current stress of converter under EPS control is
max = V1
i
4fsL
1
k
(1 − D1) + (2D1 + 2D2 − 1)
. (48)
The transmission power is
P
= nV1V2
2fsL
D2(1 − D2) +
1
2D1(1 − D1 − 2D2 )
. (49)
The backflow power is
P
bf = nV1V2 [(1/k)(1 − D1) + (2D2 − 1)]2
16fsL(1/k) + 1) . (50)
In (48)–(50), the constraints are k 1, 0 ≤ D1 ≤ 1, 0 ≤ D2 ≤
1 and 0 ≤ D1+D2 ≤ 1. Similarly, the current stress of converter
under TPS control is
imax = V1
4fsL
(2D − 1 + (1/k). (51)
The transmission power is
P = nV1V2
2fsL
D(1 − D). (52)
The backflow power is
Pbf = nV1V2 [(1/k) + (2D − 1)]2
16fsL(1/k) + 1) . (53)
In (51)–(53), the constraints are k 1 and 0 ≤ D ≤ 1. Due to
1/k 1, comparing (48)–(53) with (9)–(12) and (14)–(16), we
can come to the conclusion that the performance at k 1 is
coincident with that at k 1.
The transmission power and output voltage are both in closed-loop
control for 1160W and 180V, respectively. Fig. 19 shows
the experimental waveforms of vh1, vh2 , and iL in TPS and EPS
control for the same transmission power, and Fig. 20 shows the
curves of current stress varied with V1 and D1 . Different with
Fig. 15, the input voltage in Fig. 19 is specified as 160V, i.e.,
k = 160/(2∗180) = 0.44. As can be seen from Figs. 19 and 20,
the current stress also decreases with the increasing of D1, but
decreases with the increasing of k = V1 /(nV2 ). In fact, when k
1 (nV2 V1 ), the current stress changes into an increasewith the
increasing of voltage conversion ratio 1/k = nV2 / V1 . Similarly,
the EPS control always can generate less current stress than the
TPS control does with the condition of k 1.
Fig. 21 shows the efficiency curves of the converter in both
control methods. It can be easily found that the EPS control
can achieve higher efficiency than the TPS control, especially in
large voltage conversion ratio condition. And when the converter
is operating in the optimal point, the efficiency achieves the
maximum value.
16. ZHAO et al.: EXTENDED-PHASE-SHIFT CONTROL OF ISOLATED BIDIRECTIONAL DC–DC CONVERTER 4679
Fig. 19. Waveforms of vh1 , vh 2 , and iL in TPS and EPS control for the same transmission. (a) TPS control with V1 = 160V, V2 = 180V, and P = 1160W.
(b) EPS control with V1 = 160V, V2 = 180V, P = 1160W, and D1 = 0.2. (c) EPS control with V1 = 160V, V2 = 180V, P = 1160W, and D1 = 0.4.
Fig. 20. Curves of the current stress varied with V1 (k 1) when D1 is
specified.
VII. CONCLUSION
IBDC is an everlasting key component to realize power distri-bution
between energy generation systems and storage systems
in microgrids. In order to overcome the inherent disadvantages
of TPS control of IBDC, a novel EPS control is proposed for
power distribution in microgrid in this paper. From the theo-retical
analysis and the experiments, it can be found that EPS
control has the following features: 1) EPS control expands reg-ulating
range of transmission power and enhances regulating
flexibility. 2) EPS control reduces power-circulating flow, and
thus reduces conduction losses and improves the system effi-ciency.
3) EPS control reduces current stress, and thus reduces
switching losses and prolongs the service life of devices. For
the same power level, the devices can be selected with lower
stress levels, which saves the cost. 4) EPS control is simple in
principle and easy to implement.
REFERENCES
[1] R. H. Lasseter, “Smart distribution: Coupled microgrids,” Proc. IEEE.,
vol. 99, no. 6, pp. 1074–1082, Jun. 2011.
[2] P. Tenti, H. K. M. Paredes, and P. Mattavelli, “Conservative power the-ory,
a framework to approach control and accountability issues in smart
Fig. 21. Curves of the efficiency curves varied with V1 (k 1) when D1 is
specified.
microgrids,” IEEE Trans. Power Electron., vol. 26, no. 3, pp. 664–673,
Mar. 2011.
[3] R. Majumder, A. Ghosh, G. Ledwich, and F. Zare, “Power management
and power flow control with back-to-back converters in a utility connected
microgrid,” IEEE Trans. Power System., vol. 25, no. 2, pp. 821–834, May
2010.
[4] A. K. Abdelsalam, A. M. Massoud, S. Ahmed, and P. N. Enjeti,
“High-performance adaptive perturb and observe MPPT technique for
photovoltaic-based microgrids,” IEEE Trans. Power Electron., vol. 26,
no. 4, pp. 1010–1021, Apr. 2011.
[5] J. M. Guerrero, J. C. Vasquez, J. Matas, M. Castilla, and L. G. Vicuna,
“Control strategy for flexible microgrid based on parallel line-interactive
UPS system,” IEEE Trans. Ind. Electron., vol. 56, no. 3, pp. 726–736,
Mar. 2009.
[6] J. Y. Kim, J. H. Jeon, S. K. Kim, C. Cho, J. H. Park, H.-M. Kim,
and K.-Y. Nam, “Cooperative control strategy of energy storage system
and microsources for stabilizing the microgrid during islanded opera-tion,”
IEEE Trans. Power Electron., vol. 25, no. 12, pp. 3037–3048, Dec.
2010.
[7] J.-H. Jeon, J.Y. Kim, H. M. Kim, S.-K. Kim, C. Cho, J.-M.Kim, J.-B. Ahn,
and K.-Y. Nam, “Development of hardware in-the-loop simulation system
for testing operation and control functions of microgrid,” IEEE Trans.
Power Electron., vol. 25, no. 12, pp. 2919–2929, Dec. 2010.
[8] T. F. Wu, K. H. Sun, C. L. Kuo, and C. H. Chang, “Predictive current
controlled 5-kW single-phase bidirectional inverter with wide inductance
variation for dc-microgrid applications,” IEEE Trans. Power Electron.,
vol. 25, no. 12, pp. 3076–3084, Dec. 2010.
[9] M. G. Molina and P. E. Mercado, “Power flow stabilization and control
of microgrid with wind generation by superconducting magnetic energy
17. 4680 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 11, NOVEMBER 2012
storage,” IEEE Trans. Power Electron., vol. 26, no. 3, pp. 910–922, Mar.
2011.
[10] J. M. Gueerrero, N. Berbel, J. Matas, J. L. Sosa, and L. G. vicuna, “Droop
control method with virtual output impedance for parallel operation of
uninterruptible power supply systems in a microgrid,” in Proc. IEEE
Appl. Power Electron. Conf., 2007, pp. 1126–1132.
[11] W. Chen, P. Rong, and Z. Y. Lu, “Snubberless bidirectional DC–DC con-verter
with new CLLC resonant tank featuring minimized switching loss,”
IEEE Trans. Ind. Electron., vol. 57, no. 9, pp. 3075–3086, Sep. 2010.
[12] F. H. Khan and L. M. Tolbert, “Bi-directional power management and
fault tolerant feature in a 5-kWmultilevel DC–DC converter with modular
architecture,” IET Power Electron., vol. 2, no. 5, pp. 595–604, Jul. 2009.
[13] C. M.Wang, C. H. Lin, and T. C. Yang, “High-power-factor soft-switched
DC power supply system,” IEEE Trans. Power Electron., vol. 26, no. 2,
pp. 647–654, Feb. 2011.
[14] P. Das, S. A. Mousavi, and G. Moschopoulos, “Analysis and design of
a nonisolated bidirectional ZVS-PWM DC–DC converter with coupled
inductors,” IEEE Trans. Power Electron., vol. 25, no. 10, pp. 2630–2641,
Oct. 2010.
[15] S. Inoue and H. Akagi, “A bidirectional DC–DC converter for an energy
storage system with galvanic isolation,” IEEE Trans. Power Electron.,
vol. 22, no. 6, pp. 2299–2306, Nov. 2007.
[16] W. H. Li, W. C. Li, Y. Deng, and X. N. He, “Single-stage single-phase
high-step-up ZVT boost converter for fuel-cell microgrid system,” IEEE
Trans. Power Electron., vol. 25, no. 12, pp. 3057–3065, Dec. 2010.
[17] Y. H. Xie, J. Sun, and S. F. James, “Power flow characterization of a
bidirectional galvanically isolated high-power DC/DC converter over a
wide operating range,” IEEE Trans. Power Electron., vol. 25, no. 1,
pp. 54–65, Jan. 2010.
[18] M. Nymand and M. A. E. Andersen, “High-efficiency isolated boost DC–
DC converter for high-power low-voltage fuel-cell applications,” IEEE
Trans. Ind. Electron., vol. 57, no. 2, pp. 505–514, Feb. 2010.
[19] I. Y. Chung, W. X. Liu, K. Schoder, and D. A. Cartes, “Integration of a
bi-directional DC–DC converter model into a real-time system simulation
of a shipboard medium voltage DC system,” Int. J. Electr. Power Syst.
Res., vol. 81, pp. 1051–1059, 2011.
[20] K. R. Wang, F. C. Lee, and J. Lai, “Operation principles of bi-directional
full-bridge DC-DC converter with unified soft-switching scheme and soft-starting
capability,” in Proc. IEEE Appl. Power Electron. Conf., 2000,
pp. 111–118.
[21] C. Zhao, S.D.Round, and J.W.Kolar, “An isolated three-port bidirectional
DC–DC converter with decoupled power flowmanagement,” IEEE Trans.
Power Electron., vol. 23, no. 5, pp. 2443–2453, Sep. 2008.
[22] J. Kim, H. S. Song, and K. Nam, “Asymmetric duty control of a dual-half-
bridge dc/dc converter for single-phase distributed generators,” IEEE
Trans. Power Electron., vol. 26, no. 3, pp. 973–982, Mar. 2011.
[23] G. G. Oggier, G. O. Garcia, and A. R. Oliva, “Modulation strategy to
operate the dual active bridge DC–DC converter under soft switching in
the whole operating range,” IEEE Trans. Power Electron., vol. 26, no. 4,
pp. 1228–1236, Apr. 2011.
[24] B. Hua and M. Chris, “Eliminate reactive power and increase system
efficiency of isolated bidirectional dual-active-bridge DC–DC convert-ers
using novel dual-phase-shift control,” IEEE Trans. Power Electron.,
vol. 23, no. 6, pp. 2905–2914, Nov. 2008.
[25] H. Fan and H. Li, “A novel phase-shift bidirectional DC–DC converter
with an extended high-efficiency range for 20kVAsolid state transformer,”
in Proc. IEEE Energy Convers. Congr. Expo. (ECCE)., 2010, pp. 3870–
3876.
Biao Zhao (S’11) received the B.S. degree from the
Department of Electrical Engineering, Dalian Uni-versity
of Technology, Dalian, China, in 2009. He
is currently working toward the Ph.D. degree in the
Department of Electrical Engineering, Tsinghua Uni-versity,
Beijing, China.
His current research interests include medium-voltage
power conversion system, bidirectional iso-lated
DC–DC converters, and uninterruptible power
supply system.
Qingguang Yu (M’01) received the B.S. and M.S.
degrees from Liaoning Engineering Technology Uni-versity,
Fuxin, China, in 1989 and 1991, respectively,
and the Ph.D. degree from China University of Min-ing
and Technology, Beijing, China, in 1994, all in
electrical engineering.
After 2 years of Post-Doctoral research work in
Electrical Engineering Department, he is currently
working as an Associate Professor with the Institute
of Flexible AC Transmission System (FACTS) of Ts-inghua
University in Beijing. His current research
interests include medium-voltage power conversion system, motor drive and
control, and power system automation FACTS in power plant and station.
Weixin Sun received the B.S. degree from Yan-shan
University, Qinghuangdao, China, in 2009, and
the M.S. degree from Tsinghua University, Beijing,
China, in 2011, all in electrical engineering.
He is currently working with China Power Engi-neering
Consulting Group Corporation, North China
Power Engineering Co. Ltd.