International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
Analysis of 3 kV DC Contact Line
High-Speed Circuit Breaker Unit Protection
Scheme Limitations
Wonder Mukwata and Josiah Munda
Department of Electrical Engineering, Tshwane University of Technology, Pretoria, 0001, South Africa
Email:
[email protected],
[email protected]
Abstract—The High-Speed Circuit Breaker (HSCB) is a defacto electro-mechanical contact line protection device
employed in the 3 kV DC traction power supply system. The
breakers installed at the terminal ends of the contact line
make a unit protection scheme configuration. While the
HSCBs seem to trip under fault conditions, there is an
unknown source that keeps on supplying residual current
into the faults. This necessitates some explanation of the
source of energy of the continual flow of residual energy.
This paper makes an analysis of the limitations in the HSCB
unit protection scheme using MATLAB simulation and how
the scheme can be optimized with digital protection devices
augmented with a peer-to-peer transfer trip as an end-toend protection solution.
residual energy into the fault. This paper makes an
analysis with options to improve the limitations by
appropriating protection solutions based on open
standards with a protection and control scheme. Based on
a conception where it is controlled by autonomous
protection and control units in compliance with the
requirements for a transfer tripping system requirement,
this can guarantee that a fault on a contact line can be
sensed from the in-feed points independently.
Nomenclature
s
Distance between substation
∆s
Incremental step change in distance
Va
Substation A bus voltage
Vb
Substation B bus voltage
I
Traction current
Ia
Substation A bus instantaneous current
Ib
Substation B bus instantaneous current
Ifault
Fault current
Iafault
Fault current supplied by substation A bus
Ibfault
Fault current supplied by substation B bus
cat
Catenary wire
rcat
Catenary wire resistance
ris
Contact line resistance
Ianth
Instantaneous current supplied by Substation A
bus at the nth coordinate
Ibnth
Instantaneous current supplied by Substation B
bus at the nth coordinate
nth
nth network coordinate
zs
Contact line impedance
n
Network coordinate
con
Contact wire
rcon
Contact wire resistance
fe
Feeder wire
rfe
Feeder wire resistance
z
Per unit impedance of line
pu
Per unit
Index Terms—unit protection scheme, residual current,
residual energy, digital protection relays, peer-to-peer
transfer trip
I. INTRODUCTION
The high-speed circuit breaker (HSCB) is a critical
subsystem element of a railway electrification system.
The HSCB is the electrical interface between the traction
substation and the 3 kV DC overhead contact line
providing the fundamental element for primary protection.
The system functions in a substantially different
condition from the static nature of A.C. power plants in
that the loads in the form of electrical multiple units
(EMUs) are dynamic. This characteristic is a determinant
for discrete protection for the contact line's electrical
loading that is not constant but dependent on time
variable current loading of moving EMUs. The loading
feature made by the overlapping currents expended by the
EMUs and under fault conditions determines the
difference.
An HSCB unit protection scheme is employed in
double-fed contact line systems that use breakers at their
terminal ends with the same protection settings to detect
faults. Where faults occur, the breakers trip independently.
The breaker that is closer to the overload or fault trips
while the one that is at the remote end does not trip or
takes time to trip. Under these conditions, the breaker that
does not trip or delays in tripping keeps supplying
II. 3 KV DC CURRENT DISTRIBUTION CONCEPTS
In some railway-based mass-rapid systems, the 3 kV
DC electrification network topology comprises the
architectural design of tracks incorporating overhead
contact lines fed in parallel from adjacent substations
with a HSCB unit protection scheme. Each contact line is
Manuscript received August 5, 2021; revised December 28, 2021.
©2022 Int. J. Electron. Electr. Eng.
doi: 10.18178/ijeee.10.1.7-13
7
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
protected by de facto HSCBs at each terminal end. The
protection design typifies an open zone for island-fed
sections with an HSCB at its terminal end; and a closed
zone for contact lines protected by HSCBs at each
terminal end as elaborated by [1].
The network operates in a condition different from the
commercial and industrial enterprise’s static electrical
load profiles. The difference is in-network loading
profiles and characteristics made by overlapping current
consumed by moving EMUs electrical loads from the
substations. The EMUs network loading is characterized
by accelerating, cruising, coasting, regenerative braking,
and stopping. The EMUs motion features regular stops
and goes as it moves from station to station. While the
EMUs-motion power demand could be constant, it
creates a traveling wave of a power node that causes
power tracking in the network and shifts the current
distribution in the lines and load shift in the substations.
The loading becomes complex with multiple EMUs in a
section.
Ref. [2] gave a significant mathematical methodology
for deriving current distribution in traction networks and
its influence on current distribution for the traction
network with equal substation DC bus voltages Va = Vb,
and unequal bus voltages Va > Vb connected in parallel to
the network with the following treatment. (Va and Vb are
taken as references to the substations bus voltages in the
study. Va is substation A, and Vb is substation B bus
voltages). We can modify voltage drop calculation
equations demonstrated by [3] and come with the similar
treatment as presented by [2]. The equations from [2] and
[3] emulate real-time current distribution for substation
DC buses with equal voltages where Va = Vb and unequal
voltages where Va > Vb with currents from the
substations distributed inversely proportional to the
distances from the point of pantograph – contact wire
interface. We characterize the case of current distribution
where Va = Vb with these equations. The current tracking
characteristic on the network is a time-variant function of
an incremental step change ∆s in distance s. The current
real-time component on the nth ordinate along the line i.e.,
the instantaneous current Ia from substation A and Ib
substation B is expressed by Eq. (1) and Eq. (2) below:
𝐼𝑎ⁿᵗʰ = 𝐼. (1 −
∆𝑠
𝑠
∆𝑠
𝐼𝑏ⁿᵗʰ = 𝐼 · ( 𝑠 )
)
𝐼𝑏 = 𝐼.
𝐼𝑎 = 𝐼. (1 −
𝑠
) + ⋯ 𝐼. (1 −
∆𝑠𝑛(𝑛 + 1))/𝑠
∆𝑠2
𝑠
) … + 𝐼. (1 −
+. . . 𝐼𝑡𝑟.
∆𝑠2
𝑠
… + 𝐼. ∆𝑠𝑛(𝑛 + 1)/𝑠
𝐼𝑎ⁿᵗʰ = 𝐼𝑓𝑎𝑢𝑙𝑡. (1 −
(4)
∆𝑠
𝑠
)
(5)
𝐼𝑏ⁿᵗʰ = 𝐼𝑓𝑎𝑢𝑙𝑡 · ∆𝑠/𝑠
(6)
𝐼𝑎ⁿᵗʰ = 𝐼. (𝑠 − ∆𝑠1)/𝑠 + (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠
(7)
𝐼𝑏ⁿᵗʰ = 𝐼. (∆𝑠1)/𝑠 − (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠
(8)
A unique feature of the network scheme is found in
substations with DC bus voltages at different potentials
connected in parallel to the traction network.
Consequently, a high asymmetry of the distribution of
current occurs. [2] elaborated on this fact while [4]
further elaborated with a worked example of the
𝛿𝑉
= 0.
minimum point of potential
𝛿𝑥
The case of substations with buses at different
potential imposes loading and protection constraints. As a
result, the bus at a higher potential current loading
overlaps into the lower potential bus while the lower
potential bus diminishes supplies by a lesser load current
with a current factor (Va-Vb)/zs supplied by the higher
potential bus (where z is the resistance/impedance per
unit length of the section length). With the difference in
potential at the substation nodes, the minimum point of
potential along the contact line section is not equidistant
from the substations. This is collaborated by the extent of
the load reach of the higher potential bus comparable
with the lower potential. We characterize the case of
current distribution where Va > Vb with these equations.
Again, the current tracking characteristic on the network
is a time-variant function of distance and the time current
component on the 𝑛ᵗʰ ordinate along the line i.e. the
instantaneous current is expressed by Eq. (7):
The current from the adjacent substation with a lower
bus potential is also given by Eq. (8)
(1)
Assuming constant power demand, the instantaneous
distribution current expression for current demand per
network coordinate supplied by the substation with a
higher potential bus is given by a series in the form of Eq.
(9):
(2)
𝐼𝑎 =
𝐼.(𝑠−∆𝑠1)
(𝑉𝑎−𝑉𝑏)
𝑧𝑠
(3)
𝑠
…
+
(𝑉𝑎−𝑉𝑏)
𝑧𝑠
𝐼.(𝑠−∆𝑠(𝑛+1))
𝑠
…….
𝐼.(𝑠−∆𝑠2)
𝑠
+
+ (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠
(9)
The current from the adjacent substation with a lower
bus potential is also given by a series also in the form of
Eq. (10):
while Eq. (3) is the expression for the instantaneous
current demand distribution current for Substation A bus,
the current demand per network coordinate supplied by
the substation B bus is given by Eq. (4):
©2022 Int. J. Electron. Electr. Eng.
𝑠
These equations reveal that the load current seen by the
substation buses towards each other diminishes in inverse
proportion to the distance from either substation.
This current concept applies to fault conditions where
the prospective fault current is distributed congruently
with (1) and (2) where Ifault is the fault current at the nᵗʰ
ordinate along the line is computed from Eq. (5) and Eq.
(6):
Assuming that there is a constant power demand, the
instantaneous distribution current expression for current
demand per network coordinate I supplied by substation
A bus is given by Eq. (3):
∆𝑠1
∆𝑠1
𝐼𝑏 =
8
𝐼.∆𝑠1
𝑠
−
(𝑉𝑎−𝑉𝑏)
𝑧𝑠
…
𝐼.∆𝑠2
𝑠
−
𝑉𝑏)/𝑧𝑠
(𝑉𝑎−𝑉𝑏)
𝑧𝑠
…
𝐼.∆𝑠𝑛(𝑛+1)
𝑠
+ (𝑉𝑎 −
(10)
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
For distributed EMUs in the section, the instantaneous
distributed current expression for total current demand
per EMU coordinate in the network supplied by
substation at a higher potential is given by Eq. (11):
III. MODELLING
Determination of conductors' thermal characteristics is
complex. Several variables, particularly environmental
factors and meteorological conditions, critically influence
the conductivity of conductor materials at any given
ambient temperature as detailed in [5] and [6]. For
consistency, the conductors' material constants are taken
at 20° C to eliminate the complexities of creating
algorithms for tracking and calculating compensation
factors required for changes in conductors' constants
exposed to varying conditions mentioned in the standards.
The substations configurations with the resultant
capacities and constants are demonstrated by [7]; with the
related contact line constants are used to derive fault
current level per network coordinate. While Infrastructure
managers do not include rail inductance constants in their
standards for short circuit calculation, [8] detailed the
analysis of appropriate electrical impedance models for
steel railway rails suitable for power supply transient
fault calculations. In an r + jx inductive circuit, an AC
short-circuit current comprises decaying AC and
decaying DC components. Contrary to DC systems short
circuit calculations, inductance is often ignored. In DC
contact line systems, steel rails are used as return
conductors. Based on [9], steel rail inductance is going to
be adopted and assumed to moderate the time constant of
the network as clarified by [10] and [11].
The contact line profile is made up of
• 161 mm2 hard-drawn grooved copper contact wire
(con) with its resistance stipulated in BS EN
50149 (2012)
• 80 mm2 hard-drawn copper stranded catenary wire
(cat) with its resistance stipulated in SANS 182-1
(2008)
• 500 mm2 stranded aluminium feeder wire (fe) with
its resistance stipulated in IEC-SANS 182-2
(2008).
The resistance of the conductors is at an ambient
temperature of 20°C. The resistance of a 3 kV DC contact
line with the parallel conductors is given per unit length
given by
𝑠=𝑛+1
𝑓(𝑠𝑎) = I ∑𝑠=1
((𝑠 − ∆𝑠1)/𝑠) + (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠) + (𝑠 −
∆𝑠2)/𝑠) + (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠 … + (𝑠 − ∆𝑠𝑛(𝑛 + 1)/𝑧𝑠 + (𝑉𝑎 −
𝑉𝑏)/𝑧𝑠))
(11)
While that supplied by the adjacent substation is
shown in Eq. (12):
𝑠=𝑛+1
𝑓(𝑠𝑏) = I ∑𝑠=1
((𝑠∆𝑠1)/𝑠) − (𝑉𝑎 − 𝑉b)/𝑧𝑠) +
((𝑠∆𝑠2)/𝑠) − (𝑉𝑎 − 𝑉𝑏)/𝑧𝑠)) + ⋯ (𝑧∆𝑠(𝑛 = 1)/𝑠) − (𝑉𝑎 −
𝑉𝑏)/𝑧𝑠))
(12)
In faults and fault currents, the same argument follows
and presents a critical state for the HSCB unit protection
scheme. The scenario gets worsened by high impedance
or resistance faults that may occur below the intrinsic
breaker set values. It is not feasible within the network
configuration to implement any form of a protection
scheme with the use of HSCBs only. Nonetheless, the
network configuration is a closed zone and protection and
coordination can be employed.
In the simulation computations, it is assumed that the
contact line parameters remain constant. We treat
concept’s analysis with simplicity i.e., current
distribution for the traction network with equal substation
DC bus voltages Va = Vb. In the 3 kV DC application,
adjacent traction substations are cascaded to feed the
same contact line sections in parallel with breakers at its
terminal ends. For protection, it is the practice to use the
same overcurrent breaker setting threshold on breakers to
detect faults. When faults occur, abnormal currents flow
and trigger breakers to trip. Based on the traction network
current distribution, and breakers as stand-alone units
HSCB tripping is independent of each other when
clearing faults, i.e., the breaker that is closer to an
overload or a fault trips, while the one that is at the
remote end does not trip or takes time to trip. Under these
conditions, the breaker that does not trip or delays
tripping keeps supplying residual current into a fault.
While breakers can successfully clear faults, and with
islanded electronic control relays mounted on breaker
trolleys or cells for control, electronic control relays
independently recover supply by auto reclose. In contrast,
while line faults have not cleared, i.e., electronic control
relays independently close the HSCBs they are assigned
to "uninformed" and without coordination. The relays
have no capability of integration to synchronize and
coordinate breakers operation under fault conditions.
From a 3 kV DC network management perspective,
though HSCBs could successfully clear faults with a
lockout, control officers can reset and reclose breakers by
telemetry unaware of network status. The system cannot
manage the network. With the advent of digital devices,
the challenge remains as the devices are implemented as
uncoordinated and none-integrated stand-alone units.
©2022 Int. J. Electron. Electr. Eng.
ris = ∑𝑛𝑟=1 1/𝑟 𝑛
and for the three contact line conductor profile
1/r is = 1/r cat + 1/r fe + 1/r con
ris = (r cat . r fe . r con)/((r cat . r fe) + (r fe . r con) +
(r con . r cat))
(13)
I = Icat + Ife + Icon
(14)
Furthermore, the ampacity of the contact line is the
sum of the current flowing through each of the
conductors and is given by
The current is dependent on the impedance/resistance
of the individual conductor. Therefore, the current
flowing through the contact wire Ir𝑐𝑜𝑛 is
ris
Ircon = I. (r )
con
9
(15)
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
The current flowing through the catenary wire Ircat is
r𝑖𝑠
Ir𝑐𝑎𝑡 = I. (r𝑐𝑎𝑡)
(16)
and the current flowing through the feeder wire Ife is
ris
Ife = I. (r𝑓𝑒)
(17)
As stated by [3], the ampacity of the contact line I is
determined by the conductor that first reaches its thermal
limit. Corollary, that conductor should be protected from
thermal run away by the protection scheme.
The mathematical model, i.e., the Fourier transform of
the exponential impulse equation of short circuit response
is run on the MATLAB. The data collated from the line
constants are formatted in the current distribution
equations and converted to the algorithms that manipulate
the data in a simulation of the selected line coordinates
that output results useable for graphical analysis.
Figure 2. Fault level current distribution for: Case 1 20MVA, Case 2
15 MVA, Case 3 15 MVA and Case 4 10 MVA network capacities.
IV. SIMULATION
This
paper
presents
results
from
the
MATLAB/Simulink models and simulations to explore
the limitations in HSCB unit protection scheme. First, the
HSCB unit protection is evaluated based on Eq. (3), Eq.
(4), Eq. (5) and Eq. (6) on the phenomena of fault current
level distribution along the contact line. Then, HSCB unit
protection coordinated tripping with a peer-to-peer direct
transfer tripping scheme as an end-to-end protection
solution is explored with high impedance faults, and on
the extant of the limitation on the 3 kV DC power system
protections as depicted in Fig. 1 below.
Transducer
Contact line
Figure 3. Overall fault current in a HSCB unit protection scheme high
impedance fault clearance without telemetry (Residual current fed by
substation A during a fault clearance).
HSCB
Fig. 4 below shows the protection scheme performance
for a remote fault where the fault current magnitude is
insufficiently high such that the HSCBs cannot detect the
fault current and continue to supply energy into the fault.
HSCB calibration for protection setting sensitivity at each
end of the contact line cannot (be set to) cover the whole
length of the contact line. Where faults occur outside the
precincts of the substations, they are out of reach of
protection.
Trip signal
Fault current I
A substation
3 kV DC bus
Inter trip
Communication
media
B substation
3 kV DC bus
IED protection
Transfer trip
scheme
command send/
receive interface
Figure 1. HSCB unit protection with a peer-to-peer direct transfer
tripping scheme.
V. RESULTS ANALYSIS AND DISCUSSION
The fault current for the design matrix of the substation
switching configuration with the resultant contact line
fault current level distribution is shown Fig. 2.
The protection indecisive responses for high
impedance faults on the of the protection scheme with
and without telemetry are shown in Fig. 3-Fig. 7 for both
different input variables and fault locations. The
responses properties are discussed in the proceeding
sections.
Fig. 3 below shows the performance of the protection
scheme without telemetry. At any given time, only one
breaker is insensitive to the faults occurring in that part of
the contact line section with infinite dead time. The other
breaker detects the fault that is within its reach.
©2022 Int. J. Electron. Electr. Eng.
Figure 4. HSCB unit protection scheme distant high impedance fault
clearance performance with and without telemetry.
10
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
Fig. 5 shows the performance of the protection scheme
for remote end high impedance fault clearance
performance with and telemetry. The protection at either
end of the line positively detects the fault and provides a
high-speed inter-tripping signal. This results in both
breakers tripping instantaneously and in synchronism.
Fig. 6 and Fig. 7 show the detailed fault clearance
performance from Fig. 3. In Fig. 6 below, the contact line
conductors’ current profiles of the residual fault current
distribution fed by Substation A into contact line section.
The overall fault current at the point of fault is lesser than
the HSCB protection trip setting value.
Figure 7. Conductors current profiles during circuit breaker fault
clearance by Substation B.
Figure 5. HSCB unit protection scheme remote end high impedance
fault clearance performance with and telemetry.
Figure 8. HSCB unit protection scheme protection zones.
Based on the specifications, Table 1. shows the ratings
of the conductors in columns 1 and 2. Column 3 shows
the observed conductor loading for a high impedance
fault with the sustained fault currents. The currents are
above the maximum mean loading of the conductor
continuous ratings and well above their thermal load
capacity. The resultant is the compromise of the rectifier
equipment's thermal limit. The conductors’ temperature
elevates, resulting in the impairment of the mechanical
properties of the conductors. The HSCB does not protect
the conductor that reaches its thermal limit first, but
collectively protects the three conductors compromising
that conductor reaching its thermal limit first.
In Fig. 6. Substation A breaker does not trip because
the fault current magnitude is insignificantly low below
its threshold setting. The breaker cannot detect the fault
current and continues supplying energy into the fault.
Contrary to Fig. 6 substation A, Fig. 7 substation B
HSCB, due to its proximity to the fault senses, trips, and
clears the fault. An exception lies in the midsection where
both breakers do not sense the fault, as in Fig. 4. The
contact line section is exposed to fault current in-feeds
from both ends. Protection decisiveness is not achieved
and is self-conflicted. The breaker that does not sense the
fault continues as a source of energy, supplying energy
into the fault. The HSCB calibration setting sensitivity at
one end of the line cannot cover the length of the contact
line. At any given time, only one breaker is insensitive to
the faults in that part of the contact line infinite dead time.
Figure 6. Residual fault current distribution in conductors fed by
Substation A into contact line section.
Fig. 7 details the transient time stamp on the breaker
tripping and duration of exposure of the contact line
conductors to network faults and fault current peaking in
the individual conductors at substation B.
Table 1 below shows the stead state remnant fault
current impressed on the contact line conductors from Fig.
6 statistics.
TABLE I.
CONDUCTOR RATINGS AND OBSERVED REMNANT FAULT
CURRENT
Ratings
Catenary Wire (Cat)
Contact Wire (Con)
Feeder Wire (Fe)
Continuous
5 minutes
366 A
586 A
887 A
470 A
986 A
1894 A
©2022 Int. J. Electron. Electr. Eng.
Observed
remnant fault
current Refer
to Fig. 6
384,8 A
822,9 A
1683 A
11
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
Fig. 5 shows HSCB unit protection scheme remote end
high impedance fault clearance performance with
telemetry. The exception is in the midsection, where both
breakers do not sense the fault, as shown in Fig. 4. Since
the teleprotection depends on the feedback of relay trip
signal, it is of no effect.
HSCB protection settings are calculated to ensure the
clearance of track - contact lines short circuits and not
EMUs faults or fault impedances less than their dynamic
impedances. Fig. 8. summarizes the results of the areas of
protection zones formed in the HSCB unit protection
scheme. During high impedance faults, the rate of rise
and fault current levels at the points of fault is lesser at
either of the substations. The overall fault current at the
points of fault as we traverse away from either substation
continually falls to a lesser value than the HSCB trip
setting value. Therefore, the probability of mal-operation
is prevalent. Fig. 3, Fig. 6 and Fig. 7 are fault phenomena.
The scheme cannot protect the entire contact line
section with certainty. This concurs with the findings of
[12] and [13] with respect to HSCBs that their
performance does not comply with the EN 50123 2
specifications.
Prospective short circuit currents protection is catered
for by the breaker intrinsic trip setting that is set as backup; or by the intelligent devices rate of rise of current
threshold when the gradient of the fault current lies
outside the EMUs slope of the traction current load line.
When the gradient of the fault current lies within the
EMUs slope of the traction current load line, the rate of
rise of current detection is not certain.
With EMUs’ start-up, the starting current reaches a
maximum value and reduces gradually within a specific
time interval. Though the maximum values of the starting
current in the EMUs and the fault current are comparable,
the fault current increases instantaneously, reaching a
maximum and sustains that maximum value unless
interrupted, whereas the starting current requires a
specific time to reach a maximum value, and then drops
to a minimum value. These characteristics can be used to
formulate algorithms to discriminate the EMUs starting
current from high impedance faults and critical fault
current of significantly low magnitudes.
incomplete protection coverage). [14], [15] and [16]
presented similar works on the effectiveness of the rate of
rise of current and current increment protection attributes
of the product (i.e., relay) rather than a protection scheme.
Comparatively, other than the effectiveness of the rate of
rise protection on the unit scheme, there are constraints in
the studies on the protection coordination and its
implement ability as a holistic protection scheme with
real-time communication systems.
The transfer trip concept with the rate of rise protection
minimizes the risks on protection limitation on the
exclusion of the dead zone where the protection of one
HSCB overlaps the protection of the other breaker by use
of IEDs which are communication capable. The concept
is the heartbeat of relay logic status real-time
communication between devices. The rate of rise of
current protection augmented with the transfer trip
scheme is an optimum end-to-end strategy to fully
idealise the HSCB unit protection scheme for a total 3 kV
DC contact line protection.
CONFLICT OF INTEREST
The authors declare no conflict of interest.
AUTHOR CONTRIBUTIONS
Wonder Mukwata conducted the research using
MATLAB modelling, simulation, data collation, and
analysis. Josiah Munda reviewed the scripts and approved
the final version.
ACKNOWLEDGMENT
The authors wish to thank the Tshwane University of
Technology, Department of Electrical Engineering,
Faculty of Engineering and the Built Environment for
providing the necessary resources in the computer
laboratory. They also extend their gratitude to the support
staff for their collaboration during the research.
REFERENCES
[1]
VI. CONCLUSION
[2]
The HSCB unit protection scheme is ideal for short
circuit protection. The use of the HSCB unit protection
scheme for other faults protection leads to a large blind
zones and their overlaps in the contact line section in
between the substations where high impedance faults are
of concern as explained by Fig. 4, Fig. 5 and Fig. 7. It is
not feasible to define the sensitivity for zone protection,
let alone the (blind) zone reach compensation. Neither is
it practical to define the dead zone on the contact line
section as there is no flexible methodology calculating
and selecting the settings. This compromises the
reliability of the protection scheme and the security of the
power supply. (The dead zone is that portion of the
contact line section whereby the protection scheme is not
capable of selectively discriminating the faults. There is
©2022 Int. J. Electron. Electr. Eng.
[3]
[4]
[5]
[6]
12
M. Wang, M. Abedrabo, W. Leterme, D. V. Hertem, C.
Spallarossa, S. Oukallia, L. Grammatikos, and K. Kuroda, “A
review of AC and DC protection equipment technologies:
Towards a multivendor solution,” Cigré Winnipeg, Colloquium
Study Committees A3, B4 & D1, Cigre, B4-047, 2017.
V. Sopov, E. Abramov, N. Schurov, and E. Langeman, “Traction
network currents distribution under different power supply
voltage,” Advances in Engineering Research, vol. 133, 2017.
F. Kiessling, R. Puschmann, A. Schmieder, and E. Scheider,
Contact Lines for Electric Railways: Planning, Design,
Implementation, Maintenance, 3rd ed., Erlangen, Germany:
Publicis Publishing, 2018, ch. 5, pp. 298-300.
M. Soni, P. Gupta, and U. Bhatnagar, A Course in Electrical
Power, Nai Sarak Delhi: Dhanpat Rai and Sons, 1991, Part 2, ch. 8,
Example 8.8, p. 155.
L. Staszewski and W. Rebizant, “The differences between IEEE
and CIGRE heat balance concepts for line ampacity
considerations,” in Proc. International Symposium on Modern
Electric Power Systems, 2010, pp. 1-4.
IEEE Standard for Calculating the Current-Temperature
Relationship of Bare Overhead Conductors, IEEE Std 738-2012
(Revision of IEEE Std 738-2006 - Incorporates IEEE Std 7382012 Cor 1-2013), 23 Dec. 2013.
International Journal of Electronics and Electrical Engineering Vol. 10, No. 1, March 2022
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
J. Read, “The calculation of rectifier and inverter performance
characteristics,” Journal of the Institution of Electrical EngineersPart II: Power Engineering, vol. 92, no. 29, pp. 495-509, 1945.
J. Brown, J. Allan, and B. Mellitt, “Calculation of remote short
circuit fault currents for DC railways,” IEE Proceedings B
Electric Power Applications, vol. 139, no. 4, pp. 289-294, 1992.
J. Brown, J. Allan, and B. Mellitt, “Calculation and measurement
of rail impedances applicable to remote short circuit fault currents,”
IEE Proceedings B Electric Power Applications, vol. 139, no. 4,
pp. 295-302, 1992.
P. Silvester, “Modal network theory of skin effect in flat
conductors,” Proceedings of the IEEE, vol. 54, no. 9, pp. 11471151, 1966.
P. Silvester, “The accurate calculation of skin effect in conductors
of complicated shape,” in IEEE Transactions on Power Apparatus
and Systems, vol. PAS-87, no. 3, pp. 735-742, March 1968.
A. Rojek, “Parameters of DC high-speed circuit breakers,” in Proc.
13th International Conference Modern Electrified Transport, vol.
180, 2018.
A. Rojek and M. Siderowicz, “Researches and tests of high speed
circuit breakers for rolling stock and substations in 3 kV DC
traction power systems,” Problemy Kolejnictwa, vol. 159, pp. 7-30,
2013.
E. Cinieri, S. Cosmi, A. Fumi, V. Salvatori, and W. Torto, “A new
digital protection of the 3 kV DC electric traction lines, Results of
the Application of Four Prototypes in Italy,” thesis, University of
L’ Aquila, Italy, 2020.
M. X. Li, J. H. He, Z. Q. Bo, H. T. Yip, L. Yu, and A. Klimek,
“Simulation and algorithm development of protection scheme in
DC traction system,” in Proc. 2009 IEEE Bucharest PowerTech,
2009, pp. 1-6.
M. T. Hagh, B. Nouri, M. Nouri, H. Lomei, and K. M. Muttaqi,
“A new protection scheme for the DC traction system supply,” in
©2022 Int. J. Electron. Electr. Eng.
Proc. 2015 Australasian
Conference, 2015, pp. 1-6.
Universities
Power
Engineering
Copyright © 2022 by the authors. This is an open access article
distributed under the Creative Commons Attribution License (CC BYNC-ND 4.0), which permits use, distribution and reproduction in any
medium, provided that the article is properly cited, the use is noncommercial and no modifications or adaptations are made.
Wonder Mukwata is an Electrical Specialist employed by Metrorail.
He works in the Electrical Department on roles overseeing the 3kV DC
traction power supplies and 11kV and 33kV AC primary power supplies
for the traction substations. He is actively involved in the research and
product development on the concepts and acceptance of the introduction
of Feeder Protection Relay as product solutions and their conversion to
protection solutions for the 3kV DC traction power supplies. He had
extensive exposure to the 25kV traction power supplies with the
National Railways of Zimbabwe. He has a Bachelor of Technology
degree from the University of South Africa and is currently reading for
a Master’s Degree in Engineering with the Tshwane University of
Technology in Pretoria.
Josiah Lange Munda received the MSc degree in electric power supply
from Tver State Technical University in 1991 and the DEng degree in
electrical engineering from the University of the Ryukyus in 2002. He is
currently a Professor of electrical engineering, and the Assistant Dean
of postgraduate studies, research, and innovation with the Tshwane
University of Technology, South Africa. He has authored or coauthored
more than 200 articles in peer-reviewed journals, book chapters, and
international conference proceedings and journals. His main research
interests include power system analysis, energy efficiency, and demandside management and microgrids. He is a Member of IEEE and a Senior
Member of the South African Institute of Electrical Engineering.
13