Advances in Engineering Research (AER), volume 102
Second International Conference on
Mechanics, Materials and Structural Engineering (ICMMSE 2017)
Use of Recharge Impulse Technology in Deep Foundations Set-up
Wafi Bouassida1, a, Essaieb Hamdi1, b, Mounir Bouassida1, c
and Youri Kharine2, d
1
Université de Tunis El Manar – Ecole Nationale d’Ingénieurs de Tunis. LR14ES03-Ingénierie
Géotechnique, BP 37 Le Belvédère, 1002, Tunis, Tunisia
2
RITA FONDATIONS, Tunisia.
a
[email protected],
[email protected],
[email protected],
d
[email protected]
Keywords: RIT piles, Electrical discharge, Frictional contact, Shape effect
Abstract. This manuscript presents the use of recharge impulse technology (RIT) in pile
foundations set-up through a case study. More precisely, it discusses the performance brought by
such a technique in terms of increasing the bearing capacity of deep foundation systems comparing
to classical set-up processes. First, a historical overview about the technology and its contribution in
referenced projects is presented. Then, a discussion about the major components behind the
performance of such a technique, in pile foundation set-up, comparing to bored and driven piles is
highlighted. The final section illustrates the use of RIT through a case study.
Recharge Impulse Technology: A historical overview
RIT piles (Recharge-Impulse Technology piles), are cast-in-situ piles executed by means of high
electrical pulse compaction. In situ, once the drilling operation and installation of steel bars
elements are carried on, an injection of a 780 kg/m3 cement mortar is subjected to lateral electrical
pulse compaction. Fig. 1 presents a high voltage station ensuring the transmission of electrical
pulses to a conductive electrode which, in turns, transmits the shock wave to the surrounding soil.
As a result of this lateral compaction, the final shape of a RIT pile is therefore similar to Frankie
piles (Murthy, 2002). Hence, the diameter of such a pile is greater than the diameter of the initial
drilling. In practice, the final diameter of a RIT pile could attain 3 times the diameter of the initial
drilling thanks to high electrical pulse compaction. Since its appearance in 1999, RIT had
participated in hundreds of projects across Russia, Germany, Singapore and Tunisia. This includes
high buildings, bridges and deep excavations solutions. In terms of design, it has been proven that
estimated bearing capacities according to code standards and analytical methods are much lower
than real bearing capacities obtained from loading tests. Hence, it is crucial to explain the major
reasons behind this gap.
Fig. 1 Set-up process of RIT piles.
Copyright © 2017, the Authors. Published by Atlantis Press.
This is an open access article under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
259
Advances in Engineering Research (AER), volume 102
Performance of RIT Piles
Electrical Discharge. When exerting a lateral shock wave on a soil layer, relative density increases
and so on the shear strength (RITA 2008). In this context, RIT experience in saturated silty sands
had shown that horizontal compaction by electrical discharge yields to an increase of both friction
angle and cohesion (RITA 2008). Similar applications confirmed such a statement, peculiarly in
dynamic compaction of silty soils to prevent liquefaction risks (Holtz 2000). Thus, frictional contact
between a RIT pile and a set of surrounding soil layers is clearly more important than that of a
bored circular pile and the same horizons due to the electrical discharge effect. This naturally yields
to an increase in shaft bearing capacity of a RIT pile regarding bored piles. Compared to driven
piles which are also characterized by a vibration task during the set-up process, recharge impulse
technology differs in two main points. The first one is the compaction task which is done at constant
volume during RIT piles installation contrary to pile driving which allows heave during the set-up
process (Poulos and Davis 1980) and therefore volume change. The second point is related to the
type of compaction itself. Indeed, the dynamic loading force transmitted to surrounding soil layers
is not the same. For driven piles, the vibration transmitted to surrounding layers could be modeled
as a classical wave producing pore pressure dissipation. Conversely, the electrical discharge, which
can be modeled as an impulse, does not produce pore pressure dissipation as the duration of such a
blasting load is very short (An et al 2010). Therefore, it should be noted that, although driving piles
and executing RIT foundations yield to a densification of surrounding soil layers and therefore an
improvement of shaft bearing capacity, the two set-up processes differ and do not reproduce the
same effect in terms of surrounding layers improvement (increase in relative density ) and length of
influence zones. Nowadays, as pile design codes do not propose recommendations for modeling the
effect of blasting loads on surrounding soil layers and therefore on pile bearing capacities, it is
natural to find a gap between in situ load capacities of RIT piles and computed ones according to
such standards. Hence, it should be stated that an accurate modeling of the electrical discharge task
brings us closer to RIT piles behavior and, consequently, allows a more realistic estimation of RIT
load capacities.
Shape Effect. As the final shape of an installed RIT pile is not cylindrical but constituted by
superposed bulbs, it’s clear that the frictional mechanism developed when loading it differs from
which developed when loading a cylindrical pile. Indeed, when applying a vertical force on a
cylindrical pile, the frictional contact along its interface is governed at yield, by:
=
+ ′tan( )
(1)
τ is the shear stress at yield,
σ’: the effective vertical stress
ca: pile soil adhesion (lower than soil cohesion, (Poulos and Davis 1980))
δ = φ Where φ is the soil friction angle (Pucker et al. 2012)
Hence the shear stress along the interface is characterized by a friction angle lower than φ and
a pile soil adhesion lower than the surrounding soil cohesion. For the case of RIT piles, and without
considering the installation effect (dynamic lateral compaction) improving both the friction and
cohesion of the surrounding medium, the confined zones between the bulbs of a RIT pile, do not
develop a shear stress along the pile interface during the loading. Indeed, the frictional mechanism
generated during the loading task will principally be developed at the contact boundaries (CB) of
these zones, with the surrounding soil and not with the pile interface (Fig. 2). Such a mechanism,
produces therefore a vertical shear plan governed at yield by the friction angle and the cohesion of
the surrounding soil. Hence the shear stress mobilized at yield during the vertical pile loading can
be written as:
= + tan( )
(2)
c: Soil cohesion
260
Advances in Engineering Research (AER), volume 102
Fig. 2 Frictional mechanism developed when loading a RIT pile.
Consequently, and according to expressions (a) and (b) the frictional contact between a RIT pile
and a set of surrounding soils is more important than which of a cylindrical pile and the same soil
layers due to the curvy shape of the RIT pile. Such a frictional mechanism, developed when loading
a RIT pile, is similar to the frictional contact of under reamed piles, composed by bulbs, and widely
used in India (Mohan 1977, Poulos and Davis 1980). Indeed, pull-out in situ tests carried by Mohan
(1977) on such a pile class had confirmed that the frictional mechanism related to a given pile
composed by bulbs, is developed during the loading task, along the cylinder encountering the bulbs.
Consequently, the shear stress distribution will be governed by friction angles and cohesions of
surrounding soil layers (C, ) and not the shear parameters characterizing the frictional contact
between cylindrical piles and the surrounding soil layers (ca, ). Hence, and similarly to the
electrical discharge, it should be stated that the curvy shape of a RIT pile is a major parameter
increasing its shaft bearing capacity comparing to cylindrical piles. In the following, we will
investigate the contribution of these two parameters in the performance of RIT piles through a case
study.
Case Study
For the construction of a moderate high building (7 floors), the foundation solution was decided
to be a raft resting on 22.5 meters length RIT piles having a mean diameter of 0.4 meter. Table 1
and Fig. 3 present the characteristics of the soil profile in which the predicted RIT piles will be
installed.
Table 1. Cohesion and friction angle of crossed layers.
Layer
Thickness (m)
(Cohesion, friction) (kPa,°)
Clayey sand
3
25, 20
Grey carbonate clay
10
35, 4
Silty brown clay
2.5
35, 4
Grey compressible clay
27
30, 4
261
Advances in Engineering Research (AER), volume 102
Fig. 3 Limit Pressure variation in depth.
Based on Fig. 3 data, and according to pressuremeter standards the service load capacity equals
890 KN. Similarly, based on Table 1 data and following NAVFAC DM 7.2 (1984), load capacity
equals 910 KN. Fig. 4 presents two plots: The first corresponds to the results of a vertical loading
test carried on a RIT pile (L=22.5m, D=0.4m) installed in the investigated site. The second one
shows the results of a numerical model simulating a loading test (Plaxis 2D) in the same soil
horizons but on bored cylindrical pile having the same dimensions of the tested RIT pile.
Vertical load (Tones)
140
120
100
80
60
Loading test
(RP)
40
Numerical (CP)
20
0
0
5
10
Settlement (mm)
15
Fig. 4 Comparison between the behavior of a single RIT pile and a bored cylindrical pile installed in
the same soil horizons.
According to the results plotted in Fig. 4, it is clear that the load capacity of the installed RIT pile
should equal at minimum 1200 KN as this force corresponds to 3.8 millimeters of settlement that is
lower than 1% of the diameter length (Murthy, 2002). Hence, standardized codes, particularly the
pressuremeter method and NAVFAC (1984) clearly underestimate the load capacity. The gap
between estimated load capacities and the experimental one is primary due to the omission of the
electrical discharge task and the curvy shape of RIT piles as it has been discussed in the previous
section. Indeed, the frictional performance of RIT piles is clearly exposed from the difference
between the two load settlement curves shown in Fig. 4. More precisely, it’s clear that the shear
strength has been fully mobilized along the pile-soil interface for the case of the cylindrical pile
above 600 KN due to the drastic slope change of the load-settlement curve. However, the shear
strength along the RIT pile interface appears to be partially mobilized even at 1200 KN without a
significant change in the slope of its load settlement curve. Such an interpretation confirms the
frictional performance of RIT piles comparing to cylindrical piles. In order to confirm the electrical
discharge contribution to such a frictional performance, a pressuremeter test had been conducted in
262
Advances in Engineering Research (AER), volume 102
the investigated site, 7 months after the setup of the building foundation system, near an installed
RIT pile to investigate the influence of installation on surrounding soil parameters. Fig. 5, presents
the related results.
Limit Pressure (bars)
0
10
20
0
Depth (meters)
5
10
15
20
Limit
Pressure
after RIT Pile
installation
25
30
35
Fig. 5 Limit pressure profile after the installation of RIT piles.
Based on the obtained profile, the influence of the electrical discharge task is clearly shown.
Indeed, the limit pressure profile had been improved by more than 30% comparing to the initial
profile presented in Fig. 2. More precisely, estimating the load capacity according to this profile
yields to a service force of 1220 KN. This therefore, validates the important contribution of the
electrical discharge task to enhance the frictional bearing capacity of RIT piles comparing to
cylindrical piles.
Conclusion
Classical standardized codes underestimate the bearing capacities of RIT piles as there is no
account for the electrical discharge task and the curvy shape effects. Further works should axially
turn around these two components for a more realistic modeling of RIT piles behavior. Indeed, from
the case study presented herein, the omission of these two parameters produced an underestimation
of more than 30% of the real load capacity.
References
[1] V. N. S. Murthy, Geotechnical Engineering. Taylor & Francis Inc. Volume I: 1056 pages. NY,
USA, (2002).
[2] Recharge Impulse Technologies and Apparatus, Building on the basement of knowledge.
RITA Press. Volume I: 58 pages. Moscow, (2005).
[3] H. G. Poulos, E. H. Davis, Pile Foundations Analysis and Design. Jhon Wiley and Sons. 1
(1980) 397.
[4] J. An, C. Y. Tuan, F. ASCE, B. A. Cheeseman and G. A Gazonas, Simulation of Soil Behavior
under Blast Loading. Int. J. Geomech. 11(4) (2011) 323-334.
[5] T. Pucker and J. Grabe, Numerical Simulation of the Installation Process of Full Displacement
Piles. Comput. Geotech. 45 (2012) 93-106.
263