  1. Where water distribution piping can siphon water from a water heater and cause dry-firing, a vacuum relief valve shall be installed on the cold water inlet piping to the water heater.
  2. Vacuum relief valves shall comply with ANSI Z21.22/CSA 4.4 and be rated for not less than 210°F.
  3. Vacuum relief valves shall be installed at an elevation above the top of the heater tank, downstream of the shutoff valve.
  4. Vacuum relief valves shall be installed in the vertical, upright position unless otherwise permitted by the manufacturer's instructions.
  5. Vacuum relief valves size shall be 3/4" minimum nominal pipe size.
EXCEPTION: Where water heater inlet piping is smaller than 3/4" nominal pipe size, 1/2" vacuum relief valves shall be required.
See Figure 10.16.7
Figure 10.16.7
VACUUM RELIEF VALVES ON OVERHEAD WATER HEATER TANKS